Once a power swing is detected, if this trajectory enters the inner blinder, it is identified as an unstable swing, whereas, if it leaves the outer blinder without entering the inner blinder, it is identified as a stable swing, as shown in the figure below. The relay out-of-step trip (OST) logic can be implemented for unstable swing to trip when the positive impedance trajectory either enters the inner blinder zone (between inner blinders), known as Trip On-The-Way-In (TOWI), or exits the inner blinder zone knows as Trip On-The-Way-Out (TOWO).


Image Modified

Model Description


Image Modified


Input

...

In order to calculate the positive sequence impedance trajectory, the OOS relay requires the voltage and current magnitude (p.u.) as well as angle

...

(deg).

When the impedance trajectory is not between the inner blinder, Reset

...

=1 will reset the OOS and OST outputs to the Normal Condition as shown in the Relay Logic table below.

Output

The

...

OST trip signal is inverse of the OOS signal to make it compatible with the I/O 'status' pin of Positive Sequence Components.

When an unstable swing is detected, the

...

outputs change from Normal Condition to OOS Detection as per the following Relay Logic table. The OOS Detection state can be reset to Normal Condition using Reset =1 when impedance trajectory is outside the inner blinders.


Relay Logic

StateOOSOST
Normal
condition
Condition01
OOS
detected
Detection10

Settings


The settings for the OOS relay can be is summarized as follows:

Blinder Angle (deg)

The blinder angle of inclination in degrees (refer to relay characteristic figure above).

Inner Blinder (p.u.)

The perpendicular distance of inner blinder from ZTotal (refer to relay characteristic figure above).
Outer Blinder (p.u.)The perpendicular distance of outer blinder from ZTotal (refer to relay characteristic figure above).
PSB Delay (ms)The threshold time delay to distinguish between fault and power swing.
OOS Tripping logicLogicThe OST can

This can be set to either '0

' for Trip on-the-way-in (TOWI), i.e. when the

' or '1'. The OST trip signal gets activated during unstable swing according to set value.
0 : when impedance trajectory enters the inner blinder

, or to '1' for Trip on-the-way-out (TOWO), i.e. when the

zone (TOWI)
1 : when impedance trajectory leaves the inner blinder

.

zone (TOWO)

Number of RelaysSpecifies the number of relays to be modeled. This relay model can take vector inputs, and thus, can be used as more than one relay.

...