This section of the user documentation lays out some benchmarks for gauging system performance on the newest XG version of the OP5650 and OP5707 being introduced in early 2021 versus their previous generation.
Benchmark | Minimum License Required | Single-Phases Nodes | Breakers and fault (3φ) | Minimum Time-Step | Performance increase compare to previous generation |
---|---|---|---|---|---|
6-Bus Transmission System with I/Os | HXG Basic (1 core) | 18 | 3 | 5 us | 48% |
110-Bus 500 kV Transmission System | HXG Max (2 cores) | 336 | 3 | 20 us | 126% |
600-Node 20 kV Distribution System | HXG Max (2 cores) | 615 | 20 | 20 us | 161% |
Brazil 138 kV and Above Power System | HXG Max (6 cores) | 2542 | 8 | 45 us | 66% |
GHOST Microgrid | HXG Max (1 core) | 695 | 20 | 21 us | 71% |
IEEE 39-Bus New England Power System | HXG Plus (1 core) | 117 | 0 | 17 us | 110% |
Two Substations with 100 km Transmission Line | HXG Plus (1 core) | 129 | 81 | 15 us | 97% |